Technical data | KL1312 | KS1312 |
---|
Connection technology | 4-wire |
Specification | EN 61131-2, type 2 |
Number of inputs | 2 |
Nominal voltage | 24 V DC (-15 %/+20 %) |
“0“ signal voltage | -3…+5 V (EN 61131-2, type 2) |
“1“ signal voltage | 11…30 V (EN 61131-2, type 2) |
Input filter | typ. 0.2 ms |
Input current | typ. 6 mA (EN 61131-2, type 2) |
Current consumption K-bus | typ. 3 mA |
Electrical isolation | 500 V (K-bus/field potential) |
Bit width in the process image | 2 inputs |
Configuration | no address or configuration setting |
Weight | approx. 50 g |
Operating/storage temperature | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 %, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protect. class/installation pos. | IP 20/variable |
Pluggable wiring | for all KSxxxx Bus Terminals |
Approvals | CE, UL, Ex |