Mechanical values and environment

Housing materialPolyamide PA6.6
Weight
Net 0,23 kg
Ambient temperature -15 ... 40 °C  If several ESM-BA3.. devices are closely spaced under load, the max. cumulative current at the ambient temperature of T=20°C is 9A{} at T=30°C is 3A{} at T=40°C is 1A. If these currents are exceeded, a spacing of 5mm between the devices must be observed.
Degree of protectionIP20
Mechanical life
operating cycles 10 x 106
Contact materialAgSnO2
Mounting methodMounting rail 35mm according to DIN EN 60715 TH35
ConnectionConnection terminals
Length of control cable
With conductor cross-section 0.75mm2 1000 m
Safety contacts 13/14, 23/24, 33/34
Number of safety contacts 3
Auxiliary contacts 41/42
Number of auxiliary contacts 1

Electrical connection ratings

Operating voltage
AC/DC 24 V  -10% ... +10% All the electrical connections must either be isolated from the mains supply by a safety transformer according to EN 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent isolation measures.
Rated insulation voltage Ui
AC 250 V
Rated impulse withstand voltage Uimp
Leakage path/air gaps 4 kV
Overvoltage category according to IEC EN 60664-1 3
Reverse polarity protection
On version UB =24V DC
Rated supply frequency 50 ... 60 Hz
Power consumption
at 24 V DC 2,3 W
Degree of contamination (external, according to EN 60947-1) 2
Connection cross-section 0,14 ... 2,5 mm?
Test voltage
Control system/contacts 2,5 kV
Control voltage
On S11 18,6 ... 24 V 26 V  Start button
Control current
S11...S14 60 mA
LED indicator2 status displays (green) for relays K1 and K2
Safety contacts 13/14, 23/24, 33/34
Type of output
NORelay contacts, floating and positively driven (redundant) Positively driven relay according to EN 50205
Switching voltage
ACmax.250 V
DCmax.24 V
Switching current
at 24Vmin.5 mA
Cumulative currentFor all contactsmax.15 A  If several ESM-BA3.. devices are closely spaced under load, the max. cumulative current at the ambient temperature of T=20°C is 9A{} at T=30°C is 3A{} at T=40°C is 1A. If these currents are exceeded, a spacing of 5mm between the devices must be observed.
Fusing
External contact fuses (safety circuit) according to IEC 60269-110A gG (T6A / F8A)
Utilization category according to EN 60947-5-1
AC-153A , 250V
DC-133A , 24V
AC-128A ohmic load, 250V
DC-128A ohmic load, 50V
Breaking capacity according to UL8A 250V AC / 3A 24V DC per contact